SPAULDING REPORT ON THE APPLICATION OF OZONE TO WATER PURIFICATION REPORT ON THE Application of Ozone to Water Purification BY RUSSELL SPAULDING Consulting Ozone Engineer, State Department of Health ISSUED BY THE NEW YORK STATE DEPARTMENT OF HEALTH 1913 REPORT ON THE Application of Ozone to Water Purification BY RUSSELL SPAULDING * f * Consulting Ozone Engineer, State Department of Health ISSUED BY THE NEW YORK STATE DEPARTMENT OF HEALTH 1913 ALBANY J. B. LYON COMPANY, PRINTERS 19 13 General The demand for water in the United States has increased so rapidly, especially in the cities, that they must be thrown back, eventually, upon their streams as a source of supply. The amount of water used has about tripled in seventy-five years; and the populations of the cities have grown out of proportion to the population of the country at large, so that the problem of supply has become much greater. The growth of cities causes pollution of the water courses by sewage being discharged into the streams, and it has become more and more difficult, not only to get large enough water supplies, but to get pure water supplies. The enormous amount of money expended for met- ropolitan water systems like those of Boston and New York must inevitably reach a limit, and some method must be devised to purify the courses by the removal of the dirt and the destruction of the pathogenic bacteria. There have been three methods hitherto suggested. First, filtration, which is efficient but more or less cumbersome and expensive and not always practical. The second method in general use is rapid filtration for dirt and treatment of the water with chemicals, of which the most promising is chloride of lime. The third method which has been suggested is the treat- ment of water with ozone after rough filtration for coarse dirt. The use of ozone as a purifying agent has received such varied publicity that the history of the discovery and development of the gas needs but brief attention. A Dutch physicist, Van Marum, in 1783, while studying the behavior of gases in the path of electrical discharges, noted that oxygen gave a decided odor. But not until 1840 was this peculiar form of oxygen recognized as a distinct gas. In that year Friedrich Schoenbein, a German chemist and professor at the University of Basel, Switzerland, showed that oxygen, after being subjected to electrical stress, possessed peculiar chemical properties. To this gas he gave the name " ozone." The gas remained more or less of a scientific curiosity for a number of years, and the study of its properties seems not to have been attempted for practical ends until Berthelot took it up in 1890. He was followed by a long line of experimenters, most of them Europeans. Only a few of the army of experimenters made definite contributions to the advancement of the art of producing ozone in large quantities on a commercial scale and with a minimum expenditure of power. Ozone is a form of oxygen in which the atoms of the molecule have a different arrangement from that of ordinary oxygen. It is very unstable and will revert to oxygen in a very short time if left to itself. When, therefore, it is put into water it will speedily assume the condition of oxygen and be quite beyond the possibility of polluting water. Consequently its use is be- yond any criticism which may be directed at the chemical treatment which may remain as an impurity. Ozone could not be an impurity in water, for it changes instantaneously. It owes its efficiency in acting on bacteria to the fact that it cannot remain in the condition of ozone, but breaks up and forms free oxygen, which is an extremely powerful oxidizing agent. This oxidization destroys bacteria with incredible rapidity in the purification of water by ozone, which in turn leaves no trace of itself. The utility of ozone as a bactericide, through its marked oxidizing properties, was pointed out by de Meriten's in 1886 and Froelich about 1890. To-day there is little question of the efficacy of ozone as a commercial chemical and steriliz- ing agent but there are questions of practicability, related mostly to the cost of production and utilization, and to the ease of maintenance of generating apparatus. By the improvement and refinement of the generators, the cost of production has become a small part of the cost of any complete process for using ozone for purifying or bleaching. This condition arises largely through the expense of forcing contact between the ozonized air and the material to be treated. 3 The process about which most interest centers, naturally, is the purification of water. There are elements in the proposition to kill all bacteria and to get rid of organic contamination by introducing " electrified air " that appeal to the popular imagination as no proposal to filter or chemically sterilize water can. It has been demonstrated that ozone is a simple and effective sterilizing agent and leaves no residue in the water repugnant to the public mind as use of chemicals would. Whether or not an ozone plant is the best thing for a given location often simmers down to a question of the costs, and these depend to a very large extent on local conditions, so that results obtained in one place are to be applied with caution to another place and only under the advice of competent engineers. The earliest attempt to produce and utilize ozone on a commercial scale was that of Baron Tindal at Oudshoorn in Holland, in 1893. Since then great improvements have been made in ozone-generating apparatus, both from the point of view of reliability and of economy. Baron Tindal's first apparatus yielded about 2 grammes of ozone per kilowatt hour, whereas the plants now in use in Europe produce from 40 to 50 grammes per kilowatt hour. Even this efficiency can be improved on, and the United States may soon redeem itself for its slowness in adopting a system already so well developed in Europe by outstripping the old world in the production of economical apparatus. Baron Tindal was followed by such men as De Frise, Schneller, Vandersleen, Vosmaer, Otto, Abraham, Marmier, Siemens, Gerard, each contributing to the improvement of apparatus and application. That these efforts have finally placed the use of ozone on an economical commercial basis is shown by the following list of plants now in operation in Europe. The Otto and Siemens systems in use in these plants represent the best so far attained in Europe. 4 Partial List of European Plants Using Ozone for the Sterilization of Drinking Water Partial List of European Plants for the Sterilization of Drinking Wate: by Means of Ozone Gallons Water Name of Town Date of Installation Treated Per 24 Hours France: Marseilles ..Mediterranean Brewery 1902 129,6ocl Marseilles . .Electrical Exposition 1908 64,80c Marseilles . . Municipal Plant 19IO 75,60c Nice . . Municipal Nice . .Bon Voyage Plant 1905 6,480,00c Nice . . Rimiez Plant 1909 3,780,00c Cosne . . Municipal 1906 648,00c Paris . . Municipal 1907 648,00c Paris . . St. Maur Plant 19IO 24,100,00c Dinard . .Municipal 1907 135,00c Dinard . . Municipal 1909 162,00c Chartres . . Municipal 1908 1,620,00c Armentieres . . Municipal 1909 972,00c Avranches . . Municipal 1912 621,00c Saint-Brieuc ..Municipal 1909 810,00c Saint-Servan . . Municipal 1911 1,350,00c Laval . . Municipal 1912 1,620,00c Les Sables-d'Olonne. . 19H 675,00c Villefranche 1911 7,020,00c Indret 1903 i9,44<' Toulon , .Arsenal (5 Plants) 19IO i94,4oc Toulon . .Arsenal (1 Plant) 1912 38,88c Sotteville-les-Rouen . . . . Municipal 19H 648,00c Luneville . . Municipal 1912 2,025,o°c Compiegne . . Municipal 19H 1,620,00c Lorient . . Municipal 1911 2,700,00c Roumania: Sulina . . Municipal 405, oo< Turnu-Severin . .Municipal 1,080,0c Constantza ..Municipal 1,620,01 Pietra-Neamt ..Municipal 1, i88,o< Germany: Wiesbaden . . Municipal ,. . . 1,080,0c Paderborn . . Municipal 1902 675,0c Chemnitz . . Municipal 972,oc Leipzig . . Ribeck Brewery 64,8c Hamburg . . Palmin-Werke Schlink 64,8c Hermannstadt . . Municipal 972,oc Munich . .Augustiner Brewery 64,8c 7 Name of Town Italy: Pontelongo Ravenna Spezzia Florence Rovigo . . Municipal . . Municipal . . Municipal . .Municipal . . Municipal Date of Installation Gallons Water Treated Per 24 Hours 64,800 32,400 810,000 1,350,000 540,000 Russia: Ekaterinovka Saint Petersburg Saint Petersburg . Mines Service . .Trial Plant . . Municipal 19IO 162,000 324,000 14,040,000 Spain : Madrid . . Municipal 1911 189,OOO South America: Ribeirao-Preto, Brazil. Buenos-Ayres Valparaiso 324,000 64,800 64,800 Total joint daily capacity of above plants in gallons per 24 hours 84,308,920 8 The Plant at Saint Maur Supplying the City of Paris Daily with 24,300,000 Gallons of Sterilized Water The Plant at Saint Maur This plant is the largest one in France. It was enlarged in 1910 to its present capacity of 24,300,000 gallons per 24 hours and is the outcome of the crude attempts of Tindal in 1895. It has been remodeled many times and to-day embodies the cumulative benefits of the efforts of Tindal, Otto, Marmier, Abraham and Siemens. This plant is situated near Paris on the River Marne. The water pumped from the rivei is first filtered through sand and then sterilized by means of ozone. This ozone is drawn into the water by Otto aspirators. The water then trickles dowr through gravel contained in a sterilizing tower, meeting an ascending current of ozone which further sterilizes it. From this tower the sterilized water runs into a large reservoir, from which it is pumped into the city of Paris proper. 11 GENERAL PLAN OF THE INSTALLATION OF THE CITY OF PARIS AT THE MUNICIPAL PLANT AT SAINT MAUR City of Paris - Plant at Saint Maur BATTERY OF OTTO OZONISERS INSTALLED AT THE MUNICIPAL PLANT OF THE CITY OF PARIS AT SAINT MAUR City of Paris - Plant at Saint Maur GENERAL PLAN OF THE INSTALLATION WITH EMULSIFIER ONLY output: 100,000 liters per hour Elevation-Section City of Paris Plant at Saint Maur Plan PLAN OF INSTALLATION WITH EMULSIFIER ONLY output: ioo?ooo liters per hour Longitudinal Section General plan PLAN OF ACTUAL PLANT AT SAINT MAUR TO STUDY THE COMBINED ACTION OF THE EMULSIFIER AND THE GRAVEL GALLERY output: 100,000 liters per hour PREPARATION OF THE POROUS SLABS FOR THE CLARIFYING FILTERS CONSTRUCTION OF A FILTER-CELL Bacteriological Tests and Ozone Determinations in 1907 at Saint Maur Plant The General Ozone Company Dates Appearance Organic Matter Temperature Nitrates Nitrites Raw Exit emul- sifier Exit gallery Raw Exit emul- sifier Exit gallery Raw Exit emul- sifier Exit gallery Raw Exit emul- sifier Exit gallery Raw Exit emul- sifier Exit gallery milligr. ■milligr. milligr. degrees degrees degrees milligr. milligr. milligr. milligr. ■milligr. milligr. 1st Series - Water Filtered on the St. Maur Basins at a Rate of 2.40 Cubic Meters per Square Meter of Filter June 29, 1907.. Clear Clear Clear July 1,1907... " " " " 2, 1907... " " " " 3, 1907. " " " " 4, 1907. " " " " 5, 1907. " " " " 6, 1907... " " " " 8, 1907. " " " " 9, 1907... " " " Average... 1 1 1 :? 1.0 I. I I. I I .0 I. I 1.0 1.0 0.8 0.9 0.7 1.0 1.1 0.8 0.8 1.0 0.8 1.1 0.8 0.8 0.7 0.8 0.6 0.8 1.0 0.8 0-9 1.0 i-3 0.003 0.005 0.000 0.001 0.007 traces 0.002 O.OO3 0.000 17.0 16.3 16.8 17.0 17.1 17.2 l8.O I7.9 17-4 16.5 17.0 17-1 17-5 17-3 18.0 18.0 17.2 16.5 17.0 17.2 17.6 17-3 18.0 18.0 0.8 1.0 i-3 0.9 0.9 1.2 0.000 traces 0.000 0.9 0.8 0.9 1.0 1.2 1.2 traces 0.000 traces a 0.000 0.000 I .0 0.9 0.8 17.2 17-4 17 4 Q-9 1.0 1.2 0.001 0.001 0.001 2d Series - Water Filtered on the St. Maur Basins at a Rate of 4.80 Cubic Meters per Square Meter of Filter July 16, 1907... Clear Clear " 17, 1907... " " " 18, 1907... " " " 19,1907... " " " 20,1907... " " " 21, 1907 Clear a I .0 0.8 0.8 0.6 0.8 0 8 19.9 20.2 20.0 20.3 19.3 20.5 20.0 20.0 20.2 I .O 1.0 1.0 0.001 0.001 0.003 a u I .0 I .0 0.8 0.8 0.8 0.8 20.0 ■ 20.7 19.8 193 20.5 20.0 0.9 1.0 1.0 0.000 0.000 0.000 a I. I 0.8 1.0 0.8 1.0 0.8 0.002 0.002 0.003 " 22, 1907... Clear Clear " 23,1907... " Clear I .0 I . I 0.8 0.8 21-5 21.7 21.7 20.7 20.8 20.6 21.0 21.0 1.0 1.0 &. 10 0.000 0.003 0.004 " 24,1907... " Clear " 25,1907... " " " 26, 1907... " " Average... " " Clear a I. I 1.0 1.0 0.8 1.0 0.8 21.2 20 8 21.2 20.8 0.9 1.0 0.9 0.000 0.000 0.000 a a I. I I .0 0.8 0.8 1.0 0.9 20.8 2O.4 20.8 20.4 0.9 0.9 1.0 1.0 0.9 0.9 0.000 0.001 0.000 0.001 0.000 0.002 3d Series - Mixed Marne Filtered with 15 Per Cent Raw Marne Water Sept. 5, 1907.. Clear Clear Clear " 6,1907.. " " " " 7, 1907.. " " " " 9, 1907.. " " " " 10, 1907.. " " " " 11, 1907.. " " " " 12, 1907.. Turbid " " " 13, 1907.. " " " " 14, 1907.. " " " 1.1 1.2 1.1 1.0 0.9 0.9 1.0 i-3 1.1 1.1 1.0 0.9 0.8 0.8 0.9 0.9 i-3 0.9 1.0 1.0 0.7 0.9 0.9 0.8 0.9 1.2 1.0 19.0 18.7 20.4 20.2 19.8 20.0 19.8 19.4 19.0 18.8 19.7 20.4 20.1 19.7 20.1 19.8 19-3 19.1 18.9 19.3 20.4 20.2 19.7 20.0 19.8 19 3 1.0 1.0 1.0 1.0 1.0 1.0 0.8 0.8 1.0 1.0 1.0 0.8 1.0 0.8 1.0 1.0 1.0 1.0 0.003 0.007 0.010 0.012 0.012 0.014 0.010 0.010 0.006 0.012 0.008 0.006 0.007 0.004 0.003 0.003 0.001 O.OOI Average.. . Clear " " 1.07 0.96 0-93 19.7 19.7 19.6 1.0 0.9 1.0 0.010 0.009 0.003 4th Series - Filtered Marne Water Inoculated with Bacillus Coli Sept. 25, 1907.. Clear Clear Clear " 26, 1907.. " " Average... " " 1.2 i-3 1.2 1.1 i-3 18.0 18.2 18.0 18.0 18.2 0.7 0-7 0.8 0.7 0.7 0.003 0.003 0.003 0 • 005 0.002 i-3 1.2 18.1 18.1 0.7 - Q-7 0.003 0.003 Sept. 30, 1907.. Turbid Clear Clear Oct. 1, 1907.... " Turbid Turbid " 2, 1907 " 3, 1907 " 4, 1907 " 5> 1907 " 7, 1907 " 8, 1907 " 9, 1907 1 4 i-3 i-4 i-3 14 i-3 17.9 17-5 17-5 18.0 17.6 0.8 0.8 0.7 0.7 0.7 0.8 0.096 0.015 0.018 0015 0.015 0.020 5th Series - Raw Marne Water 6th Series - Filtered Marne Inoculated with Bacillus Coli Oct. 17, 1907... Clear Clear Clear 1.1 1.1 0.8 13.0 1 13.1 13.1 0.7 0.7 0.7 traces traces traces 15 Competition of Saint Maur - Production of Ozone (Average of 5 Experiments) The General Ozone Company Power, in kilowatts Ozone per cub. meter air, in grams Debit of air, liters per hour Production of ozonisers Power cost to produce one gram ozone, in watts-hours Debit water, liters per hour Ozone per cub. meter water, in grams Energy cost to treat one cub. meter of water, in watts-hours ist experiment 3,247 3,76o 3,373 37,588 26.38 104,030 1,191 31-42 2d 4,021 35,127 38,538 26.76 103,055 D37O 36.66 3^1 3,840 3,5io 29.51 106,692 1,250 36(89 4th 3,700 4,160 4,860 31,000 29.80 60,000 2,150 64 07 5 th 3,970 32,513 25-77 61,230 2,580 66.49 General average 27-64 ist Group of Analyses - Made at Paris - Marne Water Filtered at a Rate of 2.40 Meters Dates of Sampling Raw Water Coming from Emulsifier Coming from Gallery Ozone per cub. meter water, in grams Bacteria per c.c. B. coli in 400 c.c. Bacteria per c.c. B. coli in 400 c.c. Bacteria per c.c. B. coli in 400 c.c. June 29, 1907 580 1 3 0 I 0 1 -32 July 1, 1907 300 1 4 O 2 0 1.11 " 2, 1907 190 IO 4 0 2 0 1 23 " 3,1907 230 1 3 0 2 0 1 -30 " 4U9O7 150 b 5 0 3 0 1 25 " 5,1907 385 2 5 0 2 0 1.14 " 6, 1907 335 20 4 0 2 0 1.10 " 8, 1907 130 1 5 0 I 0 1-23 " 9, 1907 135 1 4 0 I 0 1.17 Average 270 4 4 0 i-7 0 1.20 2D Group of Analyses - Made at Paris - Marne Water Filtered Double Rate of 4.80 Meters Dates of Sampling Raw Water Coming from Emulsifier Coming from Gallery Ozone per cub. meter water, in grams Bacteria per c.c B. coli in 400 c.c. Bacteria per c.c B. coli in 400 c.c. Bacteria per c.c. B. coli in 400 c.c. July 16, 1907 75 I 2 O 2 0 1.66 " 17, 1907 US I 4 O I 0 1-35 " 18, 1907 IIO I 3 0 2 0 1.32 " 19, 1907 200 0 4 O 2 0 1.18 " 20, 1907 70 I 5 O 2 0 i-37 " 22, 1907 60 2 1 2 0 I . 20 " 23, 1907 100 0 " 24, 1907 i55 I 4 0 3 0 1-23 " 25, 1907 130 2 4 0 3 0 I 31 " 26, 1907 100 I 6 0 2 0 1.56 Average IIO I 4 0 2.1 0 135 1This experiment gave 27 bacteria per c.c. 16 Results of Bacteriological Examinations Made on Fil- tered Water Sterilized by Ozone at the Municipal Plant of the City of Paris at Saint Maur on December 10, 1909 Results at Saint Maur The water treated with ozone is the water of the River Marne during a freshet; water turgid, filtered by submerged sand. After filtration the water is clear. The cultures for bacteriological examinations were made on the spot with samples just taken. The ozone measurements were made with Potassium Iodide, Sulphuric Acid, titrated with Sodium Hyposulphite. The electrical measurements were taken directly from a wattmeter. Air and water volumes are computed from meters. The air is not dehydrated; temperature of air + o°, 5 C, temperature of water + 8°, 5 C. First Series of Experiments Water Pressure - 4 Meters Electrical energy consumed , Watts 2000 Volume of air per hour c.m. 31.020 Volume of water per hour c.m. 100.500 Volume of air per cubic meter of water c.m. 0.308 Weight of ozone per cubic meter of air gr. 4.1 Weight of ozone per cubic meter of water gr. 1.262 Bacteriological Examination Number of germs per cubic centimeter of water: Less than 1 germ in three cubic centi- meters. Absence of putrid bacteria in 100 cubic centimeters of water. Absence of coli-bacilli in 100 cubic centimeters of water. Second Series of Experiments Water Pressure - 4 Meters Electrical energy consumed Watts 1500 Volume of air per hour c.m. 31.020 Volume of water per hour c.m. 100.500 Volume of air per cubic meter of water c.m. 0.308 Weight of ozone per cubic meter of air gr. 3.1 Weight of ozone per cubic meter of water gr. 0-955 Bacteriological Examination Number of germs per cubic centimeter of water: 3 (B. mesentericus, B. megaterium). Absence of putrid bacteria in too cubic centimeters of water. Absence of coli-bacilli in 100 cubic centimeters of .water. 19 Third Series of Experiments Water Pressure - 4 Meters Electrical energy consumed Watts 1000 Volume of air per hour c.m. 31.020 Volume of water per hour c.m. 100.500 Volume of air per cubic meter of water c.m. 0.308 Weight of ozone per cubic meter of air gr. 2.2 Weight of ozone per cubic meter of water gr. 0.677 Bacteriological Examination Number of germs per cubic centimeter of water: 8 (bacillus fluorescens non liquefaciens and molds). Absence of coli-bacilli and putrid bacteria in 100 cubic centimeters of water. Fourth Series of Experiments Water Pressure - 4 Meters Electrical energy consumed Watts 750 Volume of air per hour c.m. 31.020 Volume of water per hour c.m. 100. Volume of air per cubic meter of water c.m. 0.3102 Weight of ozone per cubic meter of air gr. 1.95 Weight of ozone per cubic meter of water gr. 0.605 Bacteriological Examination Number of germs per cubic centimeter of water: 2 (bacillus fluorescens non liquefaciens). Absence of coli-bacilli and putrid bacteria in 100 cubic centimeters of water. Fifth Series of Experiments Water Pressure - 4 Meters Electrical energy consumed Watts 550 Volume of air per hour c.m. 31.020 Volume of water per hour c.m. 99. Volume of air per cubic meter of water c.m. 0.322 Weight of ozone per cubic meter of air gr. 1.450 Weight of ozone per cubic meter of water gr. 0 467 Bacteriological Examination Number of germs per cubic centimeter of water: 7. Presence of putrid bacteria in 100 cubic centimeters of water. Presence of coli-bacilli in 100 cubic centimeters of water. 20 Sixth Series of Experiments Water Pressure - 2 Meters Electrical energy consumed Watts 2000 Volume of air per hour c.m. 12. Volume of water per hour c.m. 68.95 Volume of air per cubic meter of water c.m. o. 174 Weight of ozone per cubic meter of air gr. 8.1 Weight of ozone per cubic meter of water gr. 1.409 Bacteriological Examination Number of germs per cubic centimeter of water: 1. Absence of coli-bacilli and putrid bacteria in 100 cubic centimeters of water. Seventh Series of Experiments Water Pressure - 2 Meters Electrical energy consumed Watts 1500 Volume of air per hour c.m. 12. Volume of water per hour c.m. 68.95 Volume of air per cubic meter of water c.m. o. 174 Weight of ozone per cubic meter of air gr. 6.2 Weight of ozone per cubic meter of water gr. 1.078 Bacteriological Examination Number of germs per cubic centimeter of water: 1. Absence of coli-bacilli and putrid bacteria in 100 cubic centimeters of water. Eighth Series of Experiments Water Pressure - 2 Meters Electrical energy consumed Watts 1000 Volume of air per hour c.m. 12. Volume of water per hour c.m. 68.95 Volume of air per cubic meter of water c.m. o. 174 Weight of ozone per cubic meter of air gr. 4.4 Weight of ozone per cubic meter of water gr. 0-765 Bacteriological Examination Number of germs per cubic centimeter of water: 4. Absence of coli-bacilli and putrid bacteria in 100 cubic centimeters of water. (Signed) Bonjean Paris, January io, 1910. 21 THE PURIFICATION PLANTS OF THE WATER OF THE RIVIERA, BY OZONIZED AIR (OTTO PROCESS) AND THE CITIES THUS SERVED. THE PLANTS SUPPLYING nice ARE AT A AND B. THE SHORE PLANT IS AT C The Ozone Plant at Pillefranche The Ozone Plant at Villefranche As may be seen by reference to the map, this plant supplies all the towns on the French Riviera from Villefranche to Mentone. The towns supplied are: Villefranche La Condamine Eze Saint Jean Cabbe-Roquebrune Monaco Mentone La Turbie Beaulieu Monte-Carlo The water is taken from the River Vesubie, first filtered and then sterilized by ozone. The plant was put in operation in 1911 and has a capacity of 7,020,000 gallons per 24 hours. 25 Mineral Analysis and Composition of the Filtered Water of the River Fesubie Mineral Analysis and Composition of the Water of the River Vesubie Results are expressed in milligrams per liter of water. Evaluation of organic matter in oxygen ; A11 , h ( 2. Alkaline sol. Date of Sampling Jan. 27, 1912, Turgid f 39 Feb. 12, 1912, Limpid 1.2 Feb. 25, 1912, Limpid i-5 General Research: Ammonia and salts of ammonia Traces 0 0 Albuminous nitrogen 0 0 0 Nitrites 0.006 0 0 Nitrates as (NO3H) i-3 0.8 0.9 Phosphoric acid 0 0 0 Sulphuric acid as (SO3) US- 120. 170. Chlorine as (Cl) 4.87 4.24 4- Mineral Analysis: Residuum at no° C 354- 300. 400. Residuum after calcination 502. 262. 340. Loss at red heat 52. 38. 60. Silicon as (SIO2) 16. i5- i7- Calcium as (CaO) 118. 100. 135- Magnesium as (MgO) 28. 21. 33- Probable Composition: Silicon as (SIO2) 16. i5- 19- Sulphate of calcium as (SO4Ca) 246.5 204. 272. Carbonate of calcium as (CO3Ca) 30.6 28.6 28.8 Carbonate of magnesium as (CO3Mg) 58.6 44.1 63. Chloride of sodium as (NaCl) 8.2 7.2 6-5 WATER OF THE RIVER VESUBIE Color of water: Filtered water, grayish-yellow; ozonized water, transparent blue shade. Chemical composition. The chemical composition is in no manner changed. The organic contents of the water are sensibly lessened. Putrescibility: Samples of 50 c. c. in emery-stoppered bottles maintained for 8 days at a temperature of 38° C. remained clear and odorless. Peroxide of hydrogen: No traces of peroxide of hydrogen were found in the ozonized water. Bacteria: No bacilli-coli or pathogenic bacteria were found. The above determinations were made by Mr. Elie Geneuil, expert chemist, chief of the municipal laboratory of hygiene, and of the service for the repression of fraud. 29 FILTER BASINS FOR THE PRELIMINARY CLARIFICATION OF THE WATER, BEFORE TREATING IT WITH THE ELECTRIZED AIR ENGINE ROOM OF THE PLANT OF COL DE VILLEFRANCHE THE EMULSIFIERS (LEFT) AND THE GENERATORS (RIGHT) {Apparatus patented') EMULSIFIERS AND SELF-CONTACT COLUMNS TWO UNITS OF 12,000 CUBIC METERS SUFFICE ALONE FOR THE SERVICE OF THE RIVIERA 'Apparatus patented) The Ozone Plant at Nice The Ozone Plant at Nice Early in 1904 the municipality of Nice, in Southern France, entered into a contract with the French Ozone Company for the erection of an ozone sterilization plant near the reservoir of Bon-Voyage. This plant, with a capacity of 6,480,000 gallons daily, was completed in 1905. Following are some of the requirements made by the city, translated from the official contract: 1. Capacity of sterilization, regular and continuous, 6,480,000 gallons per 24 hours. 2. Maximum allowance for upkeep $5,000 per annum. 3. The city will furnish free hydraulic power-13,157 kilogrammes on the axis of the turbines. 4. The Ozone Company guarantees that the treated water will not contain any pathogenic bacteria. 5. The maximum harmless bacteria not to exceed 10 per c. c., exception being made for B. Subtilis. 7. The Ozone Company guarantees that the chemical qualities of the water will not be altered except they be improved, that they will not introduce in the water any harmful foreign substance, and that no trace of ozone will remain in the treated water as it emits from the reservoir of Bon-Voyage. 8. The Ozone Company further guarantees the absolute inocuousness of the process. 9. The Ozone Company will be responsible for any abnormal corrosion of the conduits. 10. Price of entire installation to be 240,835 francs - $48,167. The success of this installation is evidenced by the fact that in 1909 the municipality of Nice ordered installed a second plant at Rimiez with a capacity of 3,780,000 gallons per 24 hours. 33 GENERAL ARRANGEMENT OF OTTO-ABRAHAM-MARMIER OZONE WATER-PURIFICATION PLANT AT NICE, FRANCE VIEW OF THE PLANT OF THE GENERAL OZONE COMPANY GENERAL PLAN OF THE INSTALLATIONS The water taken from Tanchette Lake is forced by the raw water pump onto the sedimentation basins and the clarifying filters. In the sedimentation basins the water circulates from below upwards and in the filters from above downwards. GENERAL PLAN OF THE INSTALLATIONS (CONTINUED) Coming from the filters, the water is received in a cistern and forced to the apparatus for sterilization. To the right is the producer gas engine which furnishes the necessary power for the functionment of the plant, the generator of electricized air, a five hundred period alternating group, and the pump for forcing the sterilized water to the city. The Ozone Plant at Paderborn, Germany The Ozone Water-Purification Plant at Paderborn, Germany As a result of the experimental plants installed at Berlin in 1896 and at Martinikenfeld in 1898, it was decided to build an ozone water-purification plant on a large scale, in order to determine whether or not it would prove reliable, efficient and economical in a municipal plant. The town of Paderborn in Germany was chosen for the initial plant. The plant was erected and officially turned over to the municipal authorities in the month of August, 1902. The plant has a capacity of 500,000 gallons of sterilized water per 24 hours. It has been operating uninterruptedly since 1902, never once failing to perform its duties in an entirely satisfactory manner. Bacteriological Examinations Bacteriological examinations are made regularly and at frequent intervals each day. Since the day the plant started, in 1902, these examinations have shown an entire absence of pathogenic bacteria. Schierstein Plant A duplicate of the Paderborn plant was erected in 1903 to supply the town of Wiesbaden, fhe plant is located near the River Rhine at Schierstein, and the sterilized water is pumped over to Wiesbaden. 37 SECTIONAL VIEWS OF THE SCHIERSTEIN, WIESBADEN, OZONE WATER-TREATING PLANT The Ozone Plant at Saint Petersburg, Russia The Ozone Water-Purification Plant at Saint Petersburg, Russia The city of Saint Petersburg in Russia is dependent on the River Neva for the major por- tion of its municipal water supply. These waters were contaminated to an alarming extent by typhoid and cholera bacteria. After a thorough investigation of all available means for the purification of water, investi- gations which extended over a considerable period of time, the authorities of the city of Saint Petersburg decided that the most reliable and effective agent was ozone. Researches made at the Pasteur Institute in Paris were made the final basis of the Russian authorities. Work on the plant was started in 1909 and was completed in November, 1910. The water after being pumped from the river is first treated with sulphate of alumina as a coagulant; it is then filtered through rapid filters. Careful bacteriological examinations show that both before and after filtration the water contains an abundance of typhoid and cholera bacteria, whereas after ozonization there is invariably a total absence of these and all other pathogenic bacteria. Cost of Purification, Etc. Gross cost, including filtration, $15.00 per million gallons. Net cost ozone sterilization, $7.50 per million gallons. 41 GENERAL PLAN OF THE OZONE WATER-PURIFICATION PLANT AT SAINT PETERSBURG OZONE BATTERIES STERILIZATION TOWER WITH EMULSIFIER PRELIMINARY CLARIFYING ARRANGEMENTS (LEFT, CLEAR CISTERN ; RIGHT, QUICK FILTER) QUICK FILTER AND AGITATORS ENGINE ROOM In Conclusion The records of the foregoing ozone purification plants, and their successful operation over an extended period of time, have established beyond cavil that ozone as a purifying agent is both efficient and economical, so that an extended discussion on the subject seems superfluous. It may be well, however, to emphasize the fact that in contradistinction to all other puri- fying agents, ozone possesses one signal virtue in that it is absolutely non-toxic. Further- more, it is insoluble in water to any appreciable extent, so that " overdosing " is impossible. Aside from its wonderful and unfailing bactericidal power, ozone totally removes from water all traces of odor, color and taste due to the decomposition of organic matter. Ozonized water is never flat to the taste - it is not only perfectly hygienic, but satisfies the most deli- cate palate. To summarize, ozone destroys in water all that which is harmful or distasteful and in no manner changes the mineral qualities. The successful application of ozone to water purification is dependent upon a number of factors, none of which may be disregarded with impunity. The failures that have occurred have been due solely to faulty design in the electrical or mechanical devices used. Ozone, as such, never has and never can fail to perform its functions properly. DEVELOPMENT 1. Economical Production The first problem that confronted the pioneers in this art was the economical production of ozone. Ozone can be produced, chemically, thermically and electrically. The first two methods were soon discarded in favor of electrical methods, which, however crude at the start, offered the best promise of ultimate success. ENERGY EXPENDED IN PRODUCING OZONE A molecule of ozone (03) weighs 16 x 3 = 48 grammes. Its production requires a heat expenditure of 29,600 calories corresponding to 0.4235 x 29,600 = 12,535 kilogrammeters. To obtain 1 gramme of ozone there is required an expenditure of energy of 0.4235 x 29,600 =261 kilogrammeters. 48 Therefore, the theoretical value of 1 horsepower (270,000 kilogrammeters) expressed in grammes of ozone is 270,000 = 1,034 grammes. 261 And the theoretical value of 1 kilowatt of electrical energy expressed in grammes of ozone is 1,034 x 1,000 = 1.386 grammes. 746 43 2. Efficiency of Production The efficiency of production of ozone is even to-day quite remote from the theoretical efficiency. The early efforts produced an efficiency of only 3 grammes of ozone per kilowatt of energy. The present efficiency, prevalent in the European plants described in this report, varies from 40 grammes to 60 grammes of ozone per kilowatt of electrical energy. In some instances much higher efficiencies have been obtained by supplementary devices, such as refrigerators and dehydration of air to be ozonized, but these devices are not only expensive and cumbersome but they tend to complicate the apparatus as a whole and diminish its dependability. Efficiency in ozone production has increased with the efficiency in electrical apparatus, such as dynamos and transformers, but little progress has been made in increasing the efficiency of the ozone apparatus itself. Aside from the generators required to supply alternating current and the transformers used to step-up the potential to its required power, the ozone apparatus consists of electrodes of metal separated by an air space, dielectrics, such as glass, being interpolated between elec- trodes to produce a brush-discharge. This brush-discharge acting on the air disturbs the atomic balance of the oxygen, which is normally di-atomic, in such a manner that more or less of the atoms recombine in an unstable tri-atomic form which is called ozone. This brush-discharge is accompanied by the phenomena of light, heat and noise, all of which absorb energy, thereby reducing the percentage of energy available for the creation of ozone. The heat generated tends to cause a reversion of ozone into oxygen and furthermore lessens the dielectric resistance of the glass dielectrics, making them liable to puncture by the high tension current - thus putting the apparatus out of commission. To overcome this difficulty various means have been resorted to, to prevent a rise in tem- perature, such as refrigerating the air before it reaches the electrodes of discharge, or surrounding the electrodes with some fluid such as oil or water, for the purpose of carrying off the heat as fast as generated. These palliatives, though they make the operation of ozone generators possible, only add to the losses already entailed in the generation of the objection- able heat. The obvious remedy for low efficiency is, therefore, to so arrange the electrical circuit that the major portion of electrical energy supplied to an ozone generator shall be used in the conversion of oxygen into ozone, and that only a small portion shall be lost in a non-productive manner. The non-production of heat should be sought rather than its elimination by cooling means. To summarize then, the main desiderata in generating ozone are: 1. A supply of alternating electric current at low cost. 2. An efficient transformer to obtain high tension. 3. Ozone electrodes that do not generate enough heat to a. Disrupt the dielectrics, b. Cause reversion of ozone to oxygen, c. Require external means for cooling. 4. Ozone electrodes that will approach the theoretical efficiency much more closely than the various systems now in use. Such an ozone generator does exist and when offered to the public will revolutionize the art. Pending such time it would be improper to give a full description of it. 3. Efficiency in Application The efficiency in the application of ozone to the purification of water is dependent entirely upon mechanicafffactors. Bacteria are immediately destroyed and converted into CO2 when brought in contact with ozone. It becomes therefore necessary to insure this contact beyond possible failure. To do this„tho water must be broken up into very fine particles and this must occur in the presence of and in contact with ozone or ozonized air at a proper concentration. 44 The only failures in ozone water-purification plants that have so far occurred have been due to a failure in breaking up the water in sufficiently fine particles and in properly contacting these small particles with ozone. I speak of failures in the technical sense, that is, failure to produce odorless, tasteless, colorless water, entirely free from pathogenic germs, by means of ozone. • Failures might occur from a commercial point of view, because of excessive overhead charges or too high a cost of maintenance due to low efficiency or unreliability of apparatus. Two much-advertised plants on the American continent - one at Lindsay, Ontario, the other at Ann Arbor, Mich.- have been failures. These failures are due only to faulty engi- neering in installation; there is an ample supply of ozone but the water is not properly broken up and contacted with the ozone. Recommendation I feel justified in urging upon the authorities of the State of New York the advisability of giving to ozone, as a means for purifying potable waters, their most earnest consideration. There is certainly no means known to science that is more reliable or absolute than ozone with which to overcome pollution and protect the public health. The latest developments in the art have brought ozone water-purification well within the boundaries of economical municipal administration. Respectfully submitted to the Commissioner of Health of the State Department of Health of the State of New York, in compliance with an order from the Commissioner dated March 11, 1913. Consulting Ozone Engineer, State Department of Health, State of New York RUSSELL SPAULDING March 25, 1913. 45